Skip to main content

Install the M.2 backplane assembly

Use this information to install the M.2 backplane assembly.

About this task

Important
Gap pad/putty pad replacement guidelines
  • To identify the gap pad/putty pad location and orientation, see:

  • Before replacing the gap pad/putty pad, gently clean the interface plate or the hardware surface with an alcohol cleaning pad.

  • Hold the gap pad/putty pad carefully to avoid deformation. Make sure no screw hole or opening is blocked by the gap pad/putty pad material.

  • Do not use expired putty pad. Check the expiry date on putty pad package. If the putty pads are expired, acquire new ones to properly replace them.

Required tools

Make sure you have the following kits to properly replace the component:
  • SD665 V3 Conduction Plate Parts

  • SD665 V3 Miscellaneous Parts Kit

  • M.2 Putty Pad Kit

    Putty pad cannot be reused. Whenever a component is removed, putty pads must be replaced with new ones before reinstalling the component.

Attention
Firmware and driver download: You might need to update the firmware or driver after replacing a component.

Procedure

  1. Replace the putty pad on bottom side of the M.2 backplane cold plate with new ones. Make sure to follow Gap pad/putty pad replacement guidelines.
    Attention

    Putty pad cannot be reused. Whenever a component is removed, putty pads must be replaced with new ones before reinstalling the component.

    Figure 1. Putty pads on the M.2 backplane cold plate (bottom side)
    Putty pads on the M.2 backplane cold plate (bottom side)
  2. Install the M.2 backplane cold plate.
    1. Place the M.2 cold plate onto the front processor (Processor 1) cold plate.
    2. Fasten the two screws to secure the M.2 backplane cold plate to the processor cold plate.
    Figure 2. M.2 backplane cold plate installation
    M.2 backplane cold plate installation
  3. Replace the putty pad on the processor (Processor 1) cold plate and the M.2 backplane cold plate with new ones. Make sure to follow Gap pad/putty pad replacement guidelines.
    Attention

    Putty pad cannot be reused. Whenever a component is removed, putty pads must be replaced with new ones before reinstalling the component.

    Figure 3. Putty pads on processor cold plate and M.2 cold plate
    Putty pads on processor cold plate and M.2 cold plate
  4. Install the M.2 backplane assembly.
    1. Connect the cable to the M.2 backplane assembly.
    2. Install the M.2 backplane assembly into the node.
    3. Secure the six screws.
    Figure 4. M.2 backplane assembly installation
    M.2 backplane assembly installation
  5. Connect the cable to the system board.
    Figure 5. M.2 backplane assembly cable installation
    M.2 backplane assembly cable installation
After you finish
  1. Install the cross braces. See Install the cross braces.

  2. Install the tray cover. See Install the tray cover.

  3. Install the tray into the enclosure. See Install a DWC tray in the enclosure.

  4. Connect all required external cables to the solution.
    Note
    Use extra force to connect QSFP cables to the solution.
  5. Check the power LED on each node to make sure it changes from fast blink to slow blink to indicate all nodes are ready to be powered on.

Demo video

Watch the procedure on YouTube