Gap pad/Putty pad identification and location

Follow the information in this section to identify their shape, location, and orientation of the various gap pads and putty pads used in SD665 V3.

Installation Guidelines for gap pad and putty pad

Attention
There are two types of thermal pad: putty pad and gap pad.
  • Gap pad—Replace gap pad if it is damaged or missing.

  • Putty pad— When replacing components, always replace putty pads with new ones.

Do not use expired putty pad. Check the expiry date on putty pad package. If the putty pads are expired, acquire new ones to properly replace them.

Water loop–Gap pad/Putty pad identification and location

Figure 1. Water loop–Gap pad/Putty pad identification and location
Water loop–Gap pad/Putty pad identification and location
Table 1. Water loop–Gap pad/Putty pad identification and location
Pad indexPad categoryAttached componentPad orientation
1Gap padWater loopGray side facing outward
2Gap padWater loopGray side facing outward
3Gap padWater loopGray side facing outward
4Putty padWater loopBoth sides can be facing outward
5Putty padWater loopBoth sides can be facing outward
6Gap padWater loopGray side facing outward
7Gap padWater loopGray side facing outward
8Gap padWater loopGray side facing outward

Components–Gap pad/Putty pad identification and location

Figure 2. Components–Gap pad/Putty pad identification and location
Components–Gap pad/Putty pad identification and location
Table 2. Components–Gap pad/Putty pad identification and location
Pad indexPad categoryAttached componentPad orientation
9Putty padPCIe riser (ConnectX-7 NDR 200)Align pad cutout to the screw hole and opening on the interface plate as shown in Install a PCIe riser assembly (ConnectX-7 NDR 200).
10Putty padPCIe riser (ConnectX-7 NDR 200)Align pad cutout to the screw hole and opening on the interface plate as shown in Install a PCIe riser assembly (ConnectX-7 NDR 200).
11Putty padPCIe riser (ConnectX-7 NDR 400)Align pad cutout to the screw hole and opening on the interface plate as shown in Install a PCIe riser assembly (ConnectX-7 NDR 400).
12Putty padM.2 backplane assemblyAlign pad cutout to the screw hole and opening on the interface plate as shown in Install the M.2 backplane assembly.
13Putty padM.2 backplane assembly
14Putty padM.2 backplane assembly
15Putty padM.2 backplane assembly
16Putty padM.2 backplane assembly
17Putty padPCIe riser (ConnectX-6)Align pad cutout to the screw hole and opening on the interface plate as shown in Install a PCIe riser assembly (ConnectX-6).
18Gap padDrive cageGray side facing outward. See Install a drive cage assembly.
19Gap padDrive cageGray side facing outward. See Install a drive cage assembly.
20Putty padConduction plate for U.3 7mm driveBoth sides can be facing outward. See Install a 7mm NVMe drive.
21Gap padDrive cage for U.3 7mm driveAlign pad cutout to the screw hole and opening on the interface plate as shown in Install a drive cage assembly
22Gap padE3.S drive 
23Putty Pad
24Putty Pad
25Gap padE3.S drive cageInstall the E3.s drive cage assembly
Pad index

26 VR 2.5 mm Putty Pad

27 VR 1.5mm Putty Pad