FQXST0524M : A temperature or voltage sensor reached a critical threshold.

A temperature or voltage sensor reached a critical threshold.

Severity

Critical

Serviceable with log

No

Automatically Notify Support

No

User Action

  1. Check that the fans in the storage system are running.
  2. Check that the ambient temperature is not too warm. The enclosure operating range is 5-40° C (41° F-104° F).
  3. Check for any obstructions to the air flow.
  4. Check that there is a module or blank filler in every module slot in the enclosure.
  5. Replace the disk or controller module that logged the error.