Install the leakage sensor

Use this information to install the leakage sensor.

About this task

Attention
Watch the procedure
  • A video of this procedure is available at YouTube.

Procedure

  1. Install the leakage sensor to the tray.
    Note
    Keep the side with LED light facing up.
    Figure 1. Installing leakage sensor

  2. Connect the leakage sensor to the power distribution board. Insert the leakage sensor cable to the cable clip.
    Figure 2. Connecting leakage sensor to the PDB

  3. Route the leakage sensor cable as shown in the illustration below. Place the end of the cable next to the PCIe x16 MCIO 4 connector on the system board in Node B. Cable-retaining tabs made of Mylar are attached to the middle and bottom wall of the tray. Insert the DIMM tool into each cable-retaining tab to open it; then, insert the leakage sensor cable into the tab.
    Figure 3. Inserting leakage sensor cable to the cable-retaining tabs

    Note
    The leakage sensor cable should be inserted into each cable-retaining tab as shown in the illustration below.
    Figure 4. Leakage sensor module inserted into the cable-retaining tabs

After you finish
  1. Install the cross braces. See Install the cross braces.

  2. Install the tray cover. See Install the tray cover.

  3. Install the tray into the enclosure. See Install a tray in the enclosure.

  4. Connect all required external cables to the solution.
    Note
    Use extra force to connect QSFP cables to the solution.
  5. Check the power LED on each node to make sure it changes from fast blink to slow blink to indicate all nodes are ready to be powered on.
    Note

    Shared I/O configuration requires specific nodes power-on sequence. When powering on the system, power on Node B first; then, power on Node A. For more information, see PCIe adapter cable routing.