FQXSPPU0001N : An Over-Temperature Condition has been detected on [ProcessorElementName].
An Over-Temperature Condition has been detected on [ProcessorElementName].
This message is for the use case when an implementation has detected an Over-Temperature Condition Detected for Processor.
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Action
Complete the following steps until the problem is solved:
- Check the event log of XClarity Controller and SMM2 Web GUI for any fan- or cooling-related issues.
- Make sure that the airflow at the front and rear of the enclosure is not obstructed and that fillers are in place, clean and correctly installed.
- Make sure that the room temperature is within operating specifications.
- Make sure that the processor 1 heat sink is securely installed.
- Make sure that the processor 1 heat sink is installed correctly and the thermal interface is correctly applied.
- (Trained technician only) Back up data and remove the existing components which have already been installed in the defective node. Then, replace the defective node tray and re-install the components.