80010701-3702ffff : Numeric sensor PEN Inlet Temp going high (upper non-critical) has asserted.
Numeric sensor PEN Inlet Temp going high (upper non-critical) has asserted.
The PEN inlet temperature has exceeded its specified threshold. The compute node has attempted a soft shutdown.
May also be shown as 800107013702ffff or 0x800107013702ffff
Severity
Warning
Alert Category
Warning - Temperature
Serviceable
Yes
SNMP Trap ID
12
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.