Skip to main content

Install a hot-swap power supply

Use this information to install a hot-swap power supply.

About this task

The following describes the information that you must consider when installing a power supply:
  • The server is shipped with only one power supply by default. In this case, the power supply is non-hot-swap and before removing it, you must turn off the server first. To support redundancy mode or hot-swap, install an additional hot-swap power supply.

  • If you are replacing the existing power supply with a new power supply:
    • Use Lenovo Capacity Planner to calculate the required power capacity for what is configured for your server. More information about Lenovo Capacity Planner is available at: Lenovo Capacity Planner website

    • Ensure that the devices that you are installing are supported. For a list of supported optional devices for the server, go to: Lenovo ServerProven website
    • Attach the power information label that comes with this option onto the existing label near the power supply.

      Figure 1. Example power supply unit label on the top cover
      Example power supply unit label on the top cover

Safety information for AC power supplies
S035
shock hazard
CAUTION

Never remove the cover on a power supply or any part that has this label attached. Hazardous voltage, current, and energy levels are present inside any component that has this label attached. There are no serviceable parts inside these components. If you suspect a problem with one of these parts, contact a service technician.

S002
disconnect all power
CAUTION
The power-control button on the device and the power switch on the power supply do not turn off the electrical current supplied to the device. The device also might have more than one power cord. To remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
S001
shock hazard
DANGER
danger
Electrical current from power, telephone, and communication cables is hazardous.

To avoid a shock hazard:

  • Connect all power cords to a properly wired and grounded electrical outlet/source.
  • Connect any equipment that will be attached to this product to properly wired outlets/sources.
  • When possible, use one hand only to connect or disconnect signal cables.
  • Never turn on any equipment when there is evidence of fire, water, or structural damage.
  • The device might have more than one power cord, to remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
Safety information for DC power supplies
CAUTION
240 V dc input (input range: 180-300 V dc) is supported in Chinese Mainland ONLY. Power supply with 240 V dc input cannot support hot plugging power cord function. Before removing the power supply with dc input, please turn off server or disconnect dc power sources at the breaker panel or by turning off the power source. Then, remove the power cord.

240 V dc warning statement

在直流输入状态下,若电源供应器插座不支持热插拔功能,请务必不要对设备电源线进行热插拔,此操作可能导致设备损坏及数据丢失。因错误执行热插拔导致的设备故障或损坏,不属于保修范围。

NEVER CONNECT AND DISCONNECT THE POWER SUPPLY CABLE AND EQUIPMENT WHILE YOUR EQUIPMENT IS POWERED ON WITH DC SUPPLY (hot-plugging). Otherwise you may damage the equipment and result in data loss, the damages and losses result from incorrect operation of the equipment will not be covered by the manufacturers’ warranty.

S035
shock hazard
CAUTION

Never remove the cover on a power supply or any part that has this label attached. Hazardous voltage, current, and energy levels are present inside any component that has this label attached. There are no serviceable parts inside these components. If you suspect a problem with one of these parts, contact a service technician.

S019
shock hazard
CAUTION
The power-control button on the device does not turn off the electrical current supplied to the device. The device also might have more than one connection to dc power. To remove all electrical current from the device, ensure that all connections to dc power are disconnected at the dc power input terminals.
S029

DANGER
danger
For -48V dc power supply, electrical current from power cables is hazardous.

To avoid a shock hazard:

  • To connect or disconnect -48V dc power cables when you need to remove/install redundancy power supply unit(s).
To Connect:To Disconnect:
  1. Turn OFF subject dc power source(s) and equipment(s) that are attached to this product.
  2. Install the power supply unit(s) into the system housing.
  3. Attach dc power cord(s) to the product.
    • Ensure correct polarity of -48 V dc connections: RTN is + and -Vin (typical -48 V) dc is -. Earth ground should be connected very well.
  4. Connect dc power cord(s) to subject power source(s).
  5. Turn ON all the power source(s).
  1. Disconnect or turn off the subject dc power source(s) (at the breaker panel) before removing the power supply unit(s).
  2. Remove the subject dc cord(s) and make sure the wire terminal of power cord(s) is insulated.
  3. Unplug the subject power supply unit(s) from the system housing.
Attention
  • Read Installation guidelines to ensure that you work safely.

  • Prevent exposure to static electricity, which might lead to system halt and loss of data, by keeping static-sensitive components in their static-protective packages until installation, and handling these devices with an electrostatic-discharge wrist strap or other grounding system.

Procedure

  1. Touch the static-protective package that contains the hot-swap power supply to any unpainted surface on the outside of the server. Then, take the hot-swap power supply out of the package and place it on a static-protective surface.
  2. If there is a power-supply filler installed, remove it.
    Figure 2. Hot-swap power supply filler removal
    Hot-swap power supply filler removal

  3. Slide the new hot-swap power supply into the bay until it snaps into position.
    Figure 3. Hot-swap power supply installation
    Hot-swap power supply installation

  4. Connect the power supply unit to a properly grounded electrical outlet.
    • For 240 V DC power supply units:

      1. Turn off the server.

      2. Connect one end of the power cord to the power connector on the power supply unit.

      3. Connect the other end of the power cord to a properly grounded electrical outlet.

    • For AC power supply units:

      1. Connect one end of the power cord to the power connector on the power supply unit.

      2. Connect the other end of the power cord to a properly grounded electrical outlet.

    • For –48V DC power supply units:

      1. Use a slotted screwdriver to loosen the 3 captive screws on the power supply terminal block.

      2. Check the type label on the power supply block and each power cord.
        TypePSU terminal blockPower cord
        Input-Vin
        GroundGND
        InputRTN
      3. Face the groove side of each power cord pin upwards, and then plug the pins into corresponding holes on the power block. Use the table above for guidance to ensure that the pins find correct slots.

      4. Tighten the captive screws on the power block. Ensure that the screws and cord pins are secured in place and no bare metal parts are shown.

      5. Connect the other end of the cables to a properly grounded electrical outlet. Ensure that the cable ends find correct outlets.