A08070802 : The specified power supply transition to critical from less severe asserted
The specified power supply transition to critical from less severe asserted
Transition to critical from less severe
Severity
Warning
Serviceable
Yes
Automatically Notify Support
No
User Action
The two power supply units installed on the server are of different input type and power rating. Complete the following steps until the problem is solved:
- Check the input type and power rating of the installed power supply units to make sure they match.
- Re-calculate the required power capacity by using Lenovo Capacity Planner (https://datacentersupport.lenovo.com/solutions/lnvo-lcp).
- Install matching power supply units (same input type and wattage) and confirm they meet the system power requirements.
- If the problem persists, collect service data log from the BMC Web interface and contact Lenovo Support (https://datacentersupport.lenovo.com/serviceprovider).