A0101200B : The specified temperature upper non recoverable going high asserted
The specified temperature upper non recoverable going high asserted
Upper Non_Recoverable-Going High
Severity
Error
Serviceable
Yes
Automatically Notify Support
Yes
User Action
Complete the following steps until the problem is solved:
- Check the BMC event logs for any cooling issues.
- Make sure that the airflow in the front and rear of the chassis is not obstructed and that fillers are correctly installed in place.
- Make sure that the room temperature is within the range specified in the operating environment specifications.
- If the problem persists, collect service data log from the BMC Web interface and contact Lenovo Support (https://datacentersupport.lenovo.com/serviceprovider).