A07030201 : The specified processor state asserted
The specified processor state asserted
State Asserted
Severity
Information
Serviceable
Yes
Automatically Notify Support
No
User Action
If the specified sensor is CPU_ALERT, replace the processor (trained technician only). If the specified sensor is CPU_Prochot, complete the following steps until the problem is solved:
- Check the BMC event logs for any fan, cooling or power related issues.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are correctly installed in place.
- Make sure that the room temperature is within the range specified in the operating environment specifications.
- If the problem persists, collect service data log from the BMC Web interface and contact Lenovo Support (https://datacentersupport.lenovo.com/serviceprovider).
- Check the BMC event logs for any fan or cooling issues.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within the range specified in operating environment specifications.
- Make sure that the processor and heat sink are securely installed.
- Make sure that the thermal grease is correctly applied.
- If the problem persists, replace the processor and heat sink(trained technician only).
- If the problem persists, collect service data log from the BMC Web interface and contact Lenovo Support (https://datacentersupport.lenovo.com/serviceprovider).