A07030201 : The specified processor state asserted

The specified processor state asserted

State Asserted

Severity

Information

Serviceable

Yes

Automatically Notify Support

No

User Action

If the specified sensor is CPU_ALERT, replace the processor (trained technician only). If the specified sensor is CPU_Prochot, complete the following steps until the problem is solved:

  1. Check the BMC event logs for any fan, cooling or power related issues.
  2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are correctly installed in place.
  3. Make sure that the room temperature is within the range specified in the operating environment specifications.
  4. If the problem persists, collect service data log from the BMC Web interface and contact Lenovo Support (https://datacentersupport.lenovo.com/serviceprovider).
If the specified sensor is CPU_Thermaltrip, complete the following steps until the problem is solved:
  1. Check the BMC event logs for any fan or cooling issues.
  2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
  3. Make sure that the room temperature is within the range specified in operating environment specifications.
  4. Make sure that the processor and heat sink are securely installed.
  5. Make sure that the thermal grease is correctly applied.
  6. If the problem persists, replace the processor and heat sink(trained technician only).
  7. If the problem persists, collect service data log from the BMC Web interface and contact Lenovo Support (https://datacentersupport.lenovo.com/serviceprovider).