80070603-2b01ffff : Sensor [SensorElementName] has transitioned to non-recoverable.

Sensor [SensorElementName] has transitioned to non-recoverable.

IMM has detected a voltage regulator error on the microprocessor and memory expansion tray.

May also be shown as 800706032b01ffff or 0x800706032b01ffff

Severity

Error

Alert Category

Critical - Power

Serviceable

Yes

CIM Information

Prefix:PLAT

and ID:0530

SNMP Trap ID

4

Automatically Notify Support

No

User Response

  • CPU 3 VRD: Indicates a problem with either the voltage regulator for CPU3 or CPU 3 itself
  • CPU 4 VRD: Indicates a problem with either the voltage regulator for CPU4 or CPU 4 itself
  • DIMM 25-30 VRD: Indicates a problem with either the voltage regulator for DIMMs 25-30 or 1 or more of the following components: DIMM25-DIMM30
  • DIMM 31-36 VRD: Indicates a problem with either the voltage regulator for DIMMs 31-36 or 1 or more of the following components: DIMM31-DIMM36
  • DIMM 37-42 VRD: Indicates a problem with either the voltage regulator for DIMMs 37-42 or 1 or more of the following components: DIMM37-DIMM42
  • DIMM 43-48 VRD: Indicates a problem with either the voltage regulator for DIMMs 43-48 or 1 or more of the following components: DIMM43-DIMM48
  1. Check the IMM Web event log. This event may be a symptom of an earlier error.
  2. Depending on the error perform the following steps.

For a CPU 3 VRD or CPU 4 VRD error:

  1. Replace the microprocessor and memory expansion tray.
  2. Replace affected microprocessor.

For a DIMM 25-30 VRD, DIMM 31-36 VRD, DIMM 37-42 VRD, or DIMM 43-48 VRD error:

  1. Replace DIMM(s) associated with error.
  2. Replace the microprocessor and memory expansion tray.