806f0107-0302ffff : An Over-Temperature Condition has been detected on [ProcessorElementName].
An Over-Temperature Condition has been detected on [ProcessorElementName].
The microprocessor 2 temperature has risen above the critical level, causing a hard shutdown of the node.
May also be shown as 806f01070302ffff or 0x806f01070302ffff
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Response
Complete the following steps:
- Check the IMM event log for any fan or cooling related issues.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
- Ensure system cover is latched properly.
- Make sure that the room temperature is within operating specifications.
- Make sure that the microprocessor 2 heat sink is securely installed.
- (Trained service technician only) Make sure that the microprocessor 2 heat sink is installed correctly and the thermal material is correctly applied.
- (Trained service technician only) Replace microprocessor 2.
Give documentation feedback