Remove the venting block (PCIe switch shuttle)

Follow instructions in this section to remove the venting block.

About this task

Attention
  • Read Installation Guidelines and Safety inspection checklist to ensure that you work safely.
  • Power off the server and peripheral devices and disconnect the power cords and all external cables. See Power off the server.
  • If the server is installed in a rack, slide the server out on its rack slide rails to gain access to the top cover, or remove the chassis from the rack. See Remove the server from rack.
  • Two people and one lifting device on site that can support up to 400 lb (181 kg) are required to perform this procedure. If you do not already have a lifting device available, Lenovo offers the Genie Lift GL-8 material lift that can be purchased at Data Center Solution Configurator. Make sure to include the Foot-release brake and the Load Platform when ordering the Genie Lift GL-8 material lift.

Procedure

  1. Make preparation for this task.
    1. Remove the PCIe switch shuttle. See Remove the PCIe switch shuttle.
  2. Remove the venting block from the PCIe switch shuttle.
    1. Unfasten the M2 screw.
    2. Lift the venting block to disengage it from the shuttle.
    Figure 1. Venting block removal
    Venting block removal

After you finish

  1. Install a replacement unit (see Install the venting block (PCIe switch shuttle)).
  2. If you are instructed to return the component or optional device, follow all packaging instructions, and use any packaging materials for shipping that are supplied to you.