Skip to main content

Thermal rules for server with 9005 series processors

This topic provides thermal rules for the server with 9005 series processors.

Abbreviations used in tables below are defined as follows:

  • Max.Temp.: Maximum ambient temperature at sea level

  • DWCM: Direct Water Cooling Module

  • FIO = riser 5 + front OCP

  • S/S: SAS/SATA

  • Any: AnyBay

  • S: standard

  • P: performance

  • A: advanced

  • NA: not applicable

  • Y: yes

  • Y* in the Support middle bays or Support rear bays column: yes (when no Gen5 7.68 TB or larger capacity NVMe drive or no Gen4 P5336 15.36 TB/30.72 TB/61.44 TB NVMe drive is installed)

  • N: no

Processor groups are defined as follows:

  • Group B: 9135

  • Group A: 9355

  • Group E1: 9555, 9655

  • Group E2: 9575F

Standard configurations

This section provides thermal information for standard configurations.

Front bays

Max. Temp.

Processor

Heat sink

Air baffle

Fan type

Support ≥ 64 GB DIMM

8 x 2.5"

16 x 2.5"

8 x 3.5"

FIO

8 x2.5"+FIO

35°C

All supported

DWCM

S

S

N

All supported

DWCM

S

P

Y

Group B

2U S

S

S

N

Group B, A

2U S

S

P

Y

Group E1

2U A

S

P

Y

30°C

All supported

DWCM

S

S

Y

Group E1

2U P

S

P

Y

Group E2

2U A

S

P

Y

25°C

Group E2

2U P

S

P

Y

Note
  • When a part with active optical cable (AOC) is installed and the rate of the part is greater than 25 GB, the ambient temperature must be limited to 30°C or lower.

  • In standard configurations with DWCM and standard fans, the ambient temperature must be limited to 30°C or lower when the following parts are installed:

    • Broadcom 57416 10GBASE-T 2-port OCP

    • Broadcom 57454 10GBASE-T 4-port OCP

Storage configurations without DWCM

This section provides thermal information for storage configurations without DWCM.

Front bays

Support middle baysSupport rear bays

Max. Temp.

Processor

Heat sink

Air baffle

Fan type

Support ≥ 64 GB DIMM

24 x 2.5"

16 x 2.5" + FIO

N

N

30°C

Group B

2U S

S

S

N

N

N

30°C

Group B

2U S

S

P

Y

N

N

30°C

Group A

2U P

S

P

N

N

N

30°C

Group E1, E2

2U A

S

P

N

N

Y*

30°C

Group B

2U P

S

P

N

Y*

N/Y*

30°C

Group B

2U P

NA

P

N

N

N

25°C

Group A, E1

2U P

S

P

Y

N

N

25°C

Group E2

2U A

S

P

Y

N

Y

25°C

Group B, A

2U P

S

P

Y

Y

N/Y

25°C

Group B, A

2U P

NA

P

Y

12 x 3.5"

N

N

30°C

Group B

2U S

S

P

Y

N

N

30°C

Group A

2U P

S

P

N

N

N

30°C

Group E1, E2

2U A

S

P

N

N

Y*

30°C

Group B

2U P

S

P

N

Y*

N/Y*

30°C

Group B

2U P

NA

P

N

N

N

25°C

Group E1

2U P

S

P

N

N

Y

25°C

Group B, A

2U P

S

P

N

Y

N/Y

25°C

Group B, A

2U P

NA

P

N

Note
  • In storage configurations without DWCM, a part with AOC and at a rate greater than 25 GB is supported under the following conditions:

    • Performance fans are used.

    • The part is not installed on slot 3.

    • The ambient temperature is 30°C or lower.

  • The following parts are not supported in storage configurations without DWCM:

    • Broadcom 57416 10GBASE-T 2-port OCP

    • Broadcom 57454 10GBASE-T 4-port OCP

Storage configurations with DWCM

This section provides thermal information for storage configurations with DWCM.

Front bays

Support middle baysSupport rear bays

Max. Temp.

Air baffle

Fan type

Support ≥ 64 GB DIMM

24 x 2.5"

16 x 2.5" + FIO

12 x 3.5"

N

N

35°C

S

S

N

N

N

30°C

S

S

Y

N

N/Y

35°C

S

P

Y

Y

N/Y

35°C

NA

P

Y

Note
  • In storage configurations with DWCM, the ambient temperature is limited to 30°C or lower when any of the following parts is installed:

    • a part with AOC and at a rate greater than 25 GB

    • Broadcom 57416 10GBASE-T 2-port OCP

    • Broadcom 57454 10GBASE-T 4-port OCP

  • In storage configurations with DWCM and middle or rear bays, the ambient temperature is limited to 30°C or lower when Gen5 7.68 TB or larger capacity NVMe drives or Gen4 P5336 15.36 TB, 30.72, or 61.44 TB NVMe drives are installed.

GPU configurations

This section provides thermal information for GPU configurations.

  • Half-height half-length (HHHL) single-wide (SW) GPU: A2, L4

  • HHHL double-wide (DW) GPU: A2000

  • Full-height full-length (FHFL) DW GPU: A30, A4500, A16, A40, A100, A6000, L40, L40S, H100, RTX 6000 Ada, RTX 4500 Ada, H100 NVL, AMD MI210

Front bays

Max. Temp.

Processor

Heat sink

Air baffle

Fan type

Max. GPU Qty.

SW

DW (A2000)

DW (A40/L40)

350W DW

Other DW

8 x 2.5"

8 x 3.5"

FIO

30°C

Group B

2U S

S

P

10

3

NA

NA

NA

Group A

2U P

S

P

10

3

NA

NA

NA

Group B, A

2U P

GPU

P

NA

NA

3

3

3

25°C

Group E1

2U P

S

P

6

3

NA

NA

NA

Group E1

2U P

GPU

P

NA

NA

2 (slot 2/5)

2 (slot 2/5)

2 (slot 2/5)

16 x 2.5"

8 x 2.5" + FIO

30°C

Group B

2U S

S

P

10

3

NA

NA

NA

Group A

2U P

S

P

10

3

NA

NA

NA

Group B, A

2U P

GPU

P

NA

NA

2 (slot 2/5)

2 (slot 2/5)

3

25°C

Group E1

2U P

S

P

6

3

NA

NA

NA

Group E1

2U P

GPU

P

NA

NA

2 (slot 2/5)

2 (slot 2/5)

2 (slot 2/5)

24 x 2.5"

16 x 2.5" + FIO

25°C

Group B

2U S

S

P

6

3

NA

NA

NA

Group A

2U P

S

P

6

3

NA

NA

NA

Group B, A

2U P

GPU

P

NA

NA

2 (slot 2/5)

2 (slot 2/5)

2 (slot 2/5)

Note

In GPU configurations with 24 x 2.5" or 16 x 2.5" + FIO front bays or GPU configurations with Group E 1 processors, a part with AOC and at a rate greater than 25 GB cannot be installed on slot 3, and the following parts are not supported:

  • Broadcom 57416 10GBASE-T 2-port OCP

  • Broadcom 57454 10GBASE-T 4-port OCP