Skip to main content

Thermal rules for server with 9005 series processors

This topic provides thermal rules for the server with 9005 series processors.

Abbreviations used in tables below are defined as follows:
  • Max.Temp.: Maximum ambient temperature at sea level

  • DWCM: Direct Water Cooling Module

  • FIO = riser 5 + front OCP

  • S/S: SAS/SATA

  • Any: AnyBay

  • S: standard

  • P: performance

  • A: advanced

  • NA: not applicable

  • Y: yes

  • Y* in the Support middle bays or Support rear bays column: yes (when no Gen5 7.68 TB or larger capacity NVMe drive or no Gen4 P5336 15.36 TB/30.72 TB/61.44 TB NVMe drive is installed)

  • N: no

Processor groups are defined as follows:
  • Group B: 9135

  • Group A: 9355

  • Group E1: 9555, 9655

  • Group E2: 9575F

Standard configurations

This section provides thermal information for standard configurations.

Front baysMax. Temp.ProcessorHeat sinkAir baffleFan typeSupport ≥ 64 GB DIMM

8 x 2.5"

16 x 2.5"

8 x 3.5"

FIO

8 x2.5"+FIO

35°CAll supportedDWCMSSN
All supportedDWCMSPY
Group B2U SSSN
Group B, A2U SSPY
Group E12U ASPY
30°CAll supportedDWCMSSY
Group E12U PSPY
Group E22U ASPY
25°CGroup E22U PSPY
Note
  • When a part with active optical cable (AOC) is installed and the rate of the part is greater than 25 GB, the ambient temperature must be limited to 30°C or lower.

  • In standard configurations with DWCM and standard fans, the ambient temperature must be limited to 30°C or lower when the following parts are installed:

    • Broadcom 57416 10GBASE-T 2-port OCP

    • Broadcom 57454 10GBASE-T 4-port OCP

Storage configurations without DWCM

This section provides thermal information for storage configurations without DWCM.

Front baysSupport middle baysSupport rear baysMax. Temp.ProcessorHeat sinkAir baffleFan typeSupport ≥ 64 GB DIMM

24 x 2.5"

16 x 2.5" + FIO

NN30°CGroup B2U SSSN
NN30°CGroup B2U SSPY
NN30°CGroup A2U PSPN
NN30°CGroup E1, E22U ASPN
NY*30°CGroup B2U PSPN
Y*N/Y*30°CGroup B2U PNAPN
NN25°CGroup A, E12U PSPY
NN25°CGroup E22U ASPY
NY25°CGroup B, A2U PSPY
YN/Y25°CGroup B, A2U PNAPY

12 x 3.5"

NN30°CGroup B2U SSPY
NN30°CGroup A2U PSPN
NN30°CGroup E1, E22U ASPN
NY*30°CGroup B2U PSPN
Y*N/Y*30°CGroup B2U PNAPN
NN25°CGroup E12U PSPN
NY25°CGroup B, A2U PSPN
YN/Y25°CGroup B, A2U PNAPN
Note
  • In storage configurations without DWCM, a part with AOC and at a rate greater than 25 GB is supported under the following conditions:
    • Performance fans are used.

    • The part is not installed on slot 3.

    • The ambient temperature is 30°C or lower.

  • The following parts are not supported in storage configurations without DWCM:

    • Broadcom 57416 10GBASE-T 2-port OCP

    • Broadcom 57454 10GBASE-T 4-port OCP

Storage configurations with DWCM

This section provides thermal information for storage configurations with DWCM.

Front baysSupport middle baysSupport rear baysMax. Temp.Air baffleFan typeSupport ≥ 64 GB DIMM

24 x 2.5"

16 x 2.5" + FIO

12 x 3.5"

NN35°CSSN
NN30°CSSY
NN/Y35°CSPY
YN/Y35°CNAPY
Note
  • In storage configurations with DWCM, the ambient temperature is limited to 30°C or lower when any of the following parts is installed:
    • a part with AOC and at a rate greater than 25 GB

    • Broadcom 57416 10GBASE-T 2-port OCP

    • Broadcom 57454 10GBASE-T 4-port OCP

  • In storage configurations with DWCM and middle or rear bays, the ambient temperature is limited to 30°C or lower when Gen5 7.68 TB or larger capacity NVMe drives or Gen4 P5336 15.36 TB, 30.72, or 61.44 TB NVMe drives are installed.

GPU configurations

This section provides thermal information for GPU configurations.

  • Half-height half-length (HHHL) single-wide (SW) GPU: A2, L4

  • HHHL double-wide (DW) GPU: A2000

  • Full-height full-length (FHFL) DW GPU: A30, A4500, A16, A40, A100, A6000, L40, L40S, H100, RTX 6000 Ada, RTX 4500 Ada, H100 NVL, AMD MI210

Front baysMax. Temp.ProcessorHeat sinkAir baffleFan typeMax. GPU Qty.
SWDW (A2000)DW (A40/L40)350W DWOther DW

8 x 2.5"

8 x 3.5"

FIO

30°CGroup B2U SSP103NANANA
Group A2U PSP103NANANA
Group B, A2U PGPUPNANA333
25°CGroup E12U PSP63NANANA
Group E12U PGPUPNANA2 (slot 2/5)2 (slot 2/5)2 (slot 2/5)

16 x 2.5"

8 x 2.5" + FIO

30°CGroup B2U SSP103NANANA
Group A2U PSP103NANANA
Group B, A2U PGPUPNANA2 (slot 2/5)2 (slot 2/5)3
25°CGroup E12U PSP63NANANA
Group E12U PGPUPNANA2 (slot 2/5)2 (slot 2/5)2 (slot 2/5)

24 x 2.5"

16 x 2.5" + FIO

25°CGroup B2U SSP63NANANA
Group A2U PSP63NANANA
Group B, A2U PGPUPNANA2 (slot 2/5)2 (slot 2/5)2 (slot 2/5)
Note
In GPU configurations with 24 x 2.5" or 16 x 2.5" + FIO front bays or GPU configurations with Group E1 processors, a part with AOC and at a rate greater than 25 GB cannot be installed on slot 3, and the following parts are not supported:
  • Broadcom 57416 10GBASE-T 2-port OCP

  • Broadcom 57454 10GBASE-T 4-port OCP