Thermal rules for server with 9005 series processors
This topic provides thermal rules for the server with 9005 series processors.
Abbreviations used in tables below are defined as follows:
Max.Temp.: Maximum ambient temperature at sea level
DWCM: Direct Water Cooling Module
FIO = riser 5 + front OCP
S/S: SAS/SATA
Any: AnyBay
S: standard
P: performance
A: advanced
NA: not applicable
Y: yes
Y* in the Support middle bays or Support rear bays column: yes (when no Gen5 7.68 TB or larger capacity NVMe drive or no Gen4 P5336 15.36 TB/30.72 TB/61.44 TB NVMe drive is installed)
N: no
Processor groups are defined as follows:
Group B: 9135
Group A: 9355
Group E1: 9555, 9655
Group E2: 9575F
Standard configurations
This section provides thermal information for standard configurations.
Front bays | Max. Temp. | Processor | Heat sink | Air baffle | Fan type | Support ≥ 64 GB DIMM |
---|---|---|---|---|---|---|
8 x 2.5" 16 x 2.5" 8 x 3.5" FIO 8 x2.5"+FIO | 35°C | All supported | DWCM | S | S | N |
All supported | DWCM | S | P | Y | ||
Group B | 2U S | S | S | N | ||
Group B, A | 2U S | S | P | Y | ||
Group E1 | 2U A | S | P | Y | ||
30°C | All supported | DWCM | S | S | Y | |
Group E1 | 2U P | S | P | Y | ||
Group E2 | 2U A | S | P | Y | ||
25°C | Group E2 | 2U P | S | P | Y |
When a part with active optical cable (AOC) is installed and the rate of the part is greater than 25 GB, the ambient temperature must be limited to 30°C or lower.
In standard configurations with DWCM and standard fans, the ambient temperature must be limited to 30°C or lower when the following parts are installed:
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP
Storage configurations without DWCM
This section provides thermal information for storage configurations without DWCM.
Front bays | Support middle bays | Support rear bays | Max. Temp. | Processor | Heat sink | Air baffle | Fan type | Support ≥ 64 GB DIMM |
---|---|---|---|---|---|---|---|---|
24 x 2.5" 16 x 2.5" + FIO | N | N | 30°C | Group B | 2U S | S | S | N |
N | N | 30°C | Group B | 2U S | S | P | Y | |
N | N | 30°C | Group A | 2U P | S | P | N | |
N | N | 30°C | Group E1, E2 | 2U A | S | P | N | |
N | Y* | 30°C | Group B | 2U P | S | P | N | |
Y* | N/Y* | 30°C | Group B | 2U P | NA | P | N | |
N | N | 25°C | Group A, E1 | 2U P | S | P | Y | |
N | N | 25°C | Group E2 | 2U A | S | P | Y | |
N | Y | 25°C | Group B, A | 2U P | S | P | Y | |
Y | N/Y | 25°C | Group B, A | 2U P | NA | P | Y | |
12 x 3.5" | N | N | 30°C | Group B | 2U S | S | P | Y |
N | N | 30°C | Group A | 2U P | S | P | N | |
N | N | 30°C | Group E1, E2 | 2U A | S | P | N | |
N | Y* | 30°C | Group B | 2U P | S | P | N | |
Y* | N/Y* | 30°C | Group B | 2U P | NA | P | N | |
N | N | 25°C | Group E1 | 2U P | S | P | N | |
N | Y | 25°C | Group B, A | 2U P | S | P | N | |
Y | N/Y | 25°C | Group B, A | 2U P | NA | P | N |
In storage configurations without DWCM, a part with AOC and at a rate greater than 25 GB is supported under the following conditions:
Performance fans are used.
The part is not installed on slot 3.
The ambient temperature is 30°C or lower.
The following parts are not supported in storage configurations without DWCM:
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP
Storage configurations with DWCM
This section provides thermal information for storage configurations with DWCM.
Front bays | Support middle bays | Support rear bays | Max. Temp. | Air baffle | Fan type | Support ≥ 64 GB DIMM |
---|---|---|---|---|---|---|
24 x 2.5" 16 x 2.5" + FIO 12 x 3.5" | N | N | 35°C | S | S | N |
N | N | 30°C | S | S | Y | |
N | N/Y | 35°C | S | P | Y | |
Y | N/Y | 35°C | NA | P | Y |
In storage configurations with DWCM, the ambient temperature is limited to 30°C or lower when any of the following parts is installed:
a part with AOC and at a rate greater than 25 GB
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP
In storage configurations with DWCM and middle or rear bays, the ambient temperature is limited to 30°C or lower when Gen5 7.68 TB or larger capacity NVMe drives or Gen4 P5336 15.36 TB, 30.72, or 61.44 TB NVMe drives are installed.
GPU configurations
This section provides thermal information for GPU configurations.
Half-height half-length (HHHL) single-wide (SW) GPU: A2, L4
HHHL double-wide (DW) GPU: A2000
Full-height full-length (FHFL) DW GPU: A30, A4500, A16, A40, A100, A6000, L40, L40S, H100, RTX 6000 Ada, RTX 4500 Ada, H100 NVL, AMD MI210
Front bays | Max. Temp. | Processor | Heat sink | Air baffle | Fan type | Max. GPU Qty. | ||||
---|---|---|---|---|---|---|---|---|---|---|
SW | DW (A2000) | DW (A40/L40) | 350W DW | Other DW | ||||||
8 x 2.5" 8 x 3.5" FIO | 30°C | Group B | 2U S | S | P | 10 | 3 | NA | NA | NA |
Group A | 2U P | S | P | 10 | 3 | NA | NA | NA | ||
Group B, A | 2U P | GPU | P | NA | NA | 3 | 3 | 3 | ||
25°C | Group E1 | 2U P | S | P | 6 | 3 | NA | NA | NA | |
Group E1 | 2U P | GPU | P | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 2 (slot 2/5) | ||
16 x 2.5" 8 x 2.5" + FIO | 30°C | Group B | 2U S | S | P | 10 | 3 | NA | NA | NA |
Group A | 2U P | S | P | 10 | 3 | NA | NA | NA | ||
Group B, A | 2U P | GPU | P | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 3 | ||
25°C | Group E1 | 2U P | S | P | 6 | 3 | NA | NA | NA | |
Group E1 | 2U P | GPU | P | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 2 (slot 2/5) | ||
24 x 2.5" 16 x 2.5" + FIO | 25°C | Group B | 2U S | S | P | 6 | 3 | NA | NA | NA |
Group A | 2U P | S | P | 6 | 3 | NA | NA | NA | ||
Group B, A | 2U P | GPU | P | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 2 (slot 2/5) |
In GPU configurations with 24 x 2.5" or 16 x 2.5" + FIO front bays or GPU configurations with Group E 1 processors, a part with AOC and at a rate greater than 25 GB cannot be installed on slot 3, and the following parts are not supported:
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP