1A07030029 : Tray 2 LeakSnsr: Other FRU, transition to Non-recoverable from less severe was asserted.
Tray 2 LeakSnsr: Other FRU, transition to Non-recoverable from less severe was asserted.
The indicated leakage sensor is detecting water leakage, need to check it.
Severity
Critical
Alert Category
System - SMM3 system event
SNMP Trap ID
111786786857
User Action
- Please power off the nodes in the indicated tray.
- Please remove the tray from the chassis, and check the leakage.
- If there is no leakage
- Please correctly install the leakage sensor.
- If the symptom persists, please replace the leakage sensor.
- If the symptom persists, please contact the technical service.
- If leakage is found, please contact the technical service.