1A0703002F : Tray 8 LeakSnsr: Other FRU, transition to Non-recoverable from less severe was asserted.

Tray 8 LeakSnsr: Other FRU, transition to Non-recoverable from less severe was asserted.

The indicated leakage sensor is detecting water leakage, need to check it.

Severity

Critical

Alert Category

System - SMM3 system event

SNMP Trap ID

111786786863

User Action

  1. Please power off the nodes in the indicated tray.
  2. Please remove the tray from the chassis, and check the leakage.
  3. If there is no leakage
    1. Please correctly install the leakage sensor.
    2. If the symptom persists, please replace the leakage sensor.
    3. If the symptom persists, please contact the technical service.
  4. If leakage is found, please contact the technical service.