80010b01-2d01ffff : Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has asserted.
Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has asserted.
The PCH temperature sensor has risen above its threshold. A hard shutdown has occurred.
May also be shown as 80010b012d01ffff or 0x80010b012d01ffff
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Response
- Check the IMM event log for any fan or cooling related issues.
- Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.
- If this is the only temperature related event and the event persists, replace the system board (Trained Service personnel only).