80070301-2c01ffff : Sensor [SensorElementName] has transitioned to non-recoverable from a less severe state.
Sensor [SensorElementName] has transitioned to non-recoverable from a less severe state.
The ML2 card has reported a non-recoverable Over temperature condition.
May also be shown as 800703012c01ffff or 0x800703012c01ffff
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- Check the IMM event log for any fan or cooling related issues.
- Make sure that the room temperature is within operating specifications.
- Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are in place and correctly installed.
- Make sure that all baffles included with the system are installed.
- Check the heatsink on the ML2 card to ensure that it is free of particulates and dust which would reduce cooling efficiency.
- Remove the heatsink on the ML2 card, check to make sure there is good contact between the heatsink and chip, and then reinstall the heatsink.