806f0a0c-2b83000c : An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on Subsystem [MemoryElementName].
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on Subsystem [MemoryElementName].
IMM determined DIMM 12 in Compute Book 3 has an Over Temperature Condition.
May also be shown as 806f0a0c2b83000c or 0x806f0a0c2b83000c
Severity
Error
Alert Category
Critical - Temperature
Serviceable
yes
SNMP Trap ID
0
Automatically Notify Support
no
User Response
Complete the following steps until problem is solved:
- Check the IMM event log for any fan or cooling related issues.
- Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.
- Check IBM Support site for Service Bulletins/RETAIN tips related to an Over Temperature Condition.
- If eXFlash DIMM, make sure the eXFlash DIMM FW is updated to the latest level.
- If the DIMM problem persists and there are no other DIMMs with the same indication, replace the DIMM.
- If the eXFlash DIMM problem persists and there are no other eXFlash DIMMs with the same indication, confirm that the eXFlash DIMM is under warranty before replacement.
Give documentation feedback