806f0a0c-2b840018 : An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on Subsystem [MemoryElementName].

An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on Subsystem [MemoryElementName].

IMM determined DIMM 24 in Compute Book 4 has an Over Temperature Condition.

May also be shown as 806f0a0c2b840018 or 0x806f0a0c2b840018

Severity​

Error

Alert Category​

Critical - Temperature

Serviceable​

yes

CIM Information​

Prefix:PLAT

and ID:0146

SNMP Trap ID​

0

Automatically Notify Support​

no

User Response​

Complete the following steps until problem is solved:

  1. Check the IMM event log for any fan or cooling related issues.
  2. Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are in place and correctly installed.
  3. Make sure that the room temperature is within operating specifications.
  4. Check IBM Support site for Service Bulletins/RETAIN tips related to an Over Temperature Condition.
  5. If eXFlash DIMM, make sure the eXFlash DIMM FW is updated to the latest level.
  6. If the DIMM problem persists and there are no other DIMMs with the same indication, replace the DIMM.
  7. If the eXFlash DIMM problem persists and there are no other eXFlash DIMMs with the same indication, confirm that the eXFlash DIMM is under warranty before replacement.