Thermal rules
This topic provides thermal rules for the server.
Server models with front drive bays only
This section provides thermal information for server models with front drive bays only.
Configuration |
| |||||
---|---|---|---|---|---|---|
Max. Ambient Temp. (at sea level) | 35°C | 30°C | ||||
CPU TDP (watts) | 185 ≤ TDP ≤ 205 | 205 < TDP ≤ 250 | 250 < TDP ≤ 300 | 300 < TDP ≤ 350 | ||
Heat sink | Standard | Performance | Performance | Performance | ||
Air baffle | √ | x | x | x | ||
Fan type | Standard | Performance | Performance | Performance | ||
DIMM capacity | ≤ 64 GB | ≤ 64 GB | ≤ 64 GB | ≤ 64 GB | ||
Max. DIMM Qty. | 32 | 32 | 32 | 32 |
Configuration |
| ||||
---|---|---|---|---|---|
Max. Ambient Temp. (at sea level) | 35°C | 30°C | |||
CPU TDP (watts) | 185 ≤ TDP ≤ 205 | 205 < TDP ≤ 250 | 250 < TDP ≤ 300 | 300 < TDP ≤ 350 | |
Heat sink | Standard | Performance | Performance | Performance | |
Air baffle | √ | x | x | x | |
DIMM capacity | ≤ 64 GB | ≤ 64 GB | ≤ 64 GB | ≤ 64 GB | |
Fan type | Performance | Performance | Performance | Performance | |
Max. DIMM Qty. | 32 | 32 | 32 | 32 |
When the server is installed with below adapters with the AOC transceiver: | Follow below rules: |
|
|
When the server is installed with rear M.2 drive assembly, must install an M.2 drive heat sink.
Server models with front and rear drive bays
This section provides thermal information for server models with front and rear drive bays.
Configuration |
| ||||
---|---|---|---|---|---|
Max. Ambient Temp. (at sea level) | 35°C | 30°C | 25°C | ||
CPU TDP (watts) | 185 ≤ TDP ≤ 205 | 225 < TDP ≤ 250 | 250 < TDP ≤ 300 | 300 < TDP ≤ 350 | |
Heat sink | Performance | Performance | Performance | Performance | |
Air baffle | x | x | x | x | |
Fan type | Performance | Performance | Performance | Performance | |
DIMM capacity | ≤ 64 GB | ≤ 64 GB | ≤ 64 GB | ≤ 64 GB | |
Max. DIMM Qty. | 32 | 32 | 32 | 32 |
When the server is installed with below adapters with the AOC transceiver: | Follow below rules: |
|
|
When the server is installed with rear M.2 drive assembly, must install an M.2 drive heat sink.
Server models with NeptAir module
This section provides thermal information for server models installed with the Processor NeptuneTM Air Module (NeptAir).
Configuration1,2 |
| ||||||
---|---|---|---|---|---|---|---|
Max. Ambient Temp. (at sea level) | 35°C | 30°C | |||||
CPU TDP (watts) | 185 ≤ TDP ≤ 205 | 205 < TDP ≤ 250 | 250 < TDP ≤ 300 | 300 < TDP ≤ 350 | |||
Heat sink | Processor NeptuneTM Air Module (NeptAir) | ||||||
Air baffle | x | ||||||
Fan type | Performance | ||||||
DIMM capacity | ≤ 64 GB | ||||||
Max. DIMM Qty. | 32 |
The server models installed with NeptAir module do not support rear drives or GPUs.
The server models installed with NeptAir module do not support 4 x 2.5'' front drives with front adapter assembly.
When the server is installed with below adapters with the AOC transceiver: | Follow below rules: |
|
|
When the server is installed with rear M.2 drive assembly, must install an M.2 drive heat sink.
Server models with NeptCore module
This section provides thermal information for server models installed with the Processor NeptuneTM Core Module (NeptCore).
Configuration |
| ||
---|---|---|---|
CPU TDP (watts) | TDP ≤ 350 | ||
Max. Ambient Temp. (at sea level) | 35°C | ||
Max. Liquid1 inlet Temp. (at sea level) | 45°C | ||
Heat sink | Processor NeptuneTM Core Module (NeptCore) | ||
Air baffle | x | ||
Fan type | Standard2,3 | ||
DIMM capacity | ≤ 64 GB | ||
Max. DIMM Qty. | 32 |
The liquid flow rate for de-ionized water should be no less than 0.5 liters per minute (lpm).
When the server is installed with any ≥ 100 GbE AOC transceiver:
With standard fan-packs, the ambient temperature must be limited to 30°C or lower.
With high-performance fan-packs, the ambient temperature must be limited to 35°C or lower.
When the server is installed with rear M.2 drive assembly, must install an M.2 drive heat sink.
When the server is installed with below adapters with the AOC transceiver: | Follow below rules: |
|
|