Thermal rules

This topic provides thermal rules for the server.

Note
  • Install the DIMM dummy for the empty DIMM slot.

  • When the server is installed with rear M.2 NVMe/SATA drive or front M.2 NVMe drive assembly, users must install an M.2 drive heat sink.

  • If one processor is installed, at least three fan-packs should be installed.

  • Users can replace the standard fans with high-performance or ultra fans for the server models not installing with Compute Complex Neptune Core Module.

  • Users can replace the standard heat sinks with high-performance heat sinks for all configurations.

Server models with front drive bays only (standard configuration)

This section provides thermal information for server models with front drive bays only.

Configuration
  • Backplane-less configuration

  • 4 x 2.5'' NVMe/SAS/SATA

  • 8 x 2.5'' SAS/SATA

  • 10 x 2.5'' SAS/SATA

  • 6 x 2.5'' SAS/SATA + 4 x 2.5'' AnyBay

Max. Ambient Temp.

(at sea level)

45°C35°C
CPU TDP (watts)TDP ≤ 165165 < TDP ≤ 210210 < TDP ≤ 350
Heat sinkStandardStandardPerformance
Air bafflex
Fan typeStandardStandardPerformance
DIMM capacity≤ 64 GB≤ 128 GB≤ 256 GB
Max. DIMM Qty.323232
Configuration
  • 8 x 2.5'' NVMe/AnyBay/U.3

  • 10 x 2.5'' NVMe/AnyBay/U.3

Max. Ambient Temp.

(at sea level)

35°C30°C
CPU TDP (watts)TDP ≤ 165165 < TDP ≤ 210210 < TDP ≤ 350TDP ≤ 165
Heat sinkStandardStandardPerformanceStandard
Air bafflex
DIMM capacity≤ 64 GB≤ 256 GB≤ 256 GB≤ 128 GB
Fan typeStandardPerformancePerformanceStandard
Max. DIMM Qty.32323232
Table 1. Special notes
When the server is installed with below adapters, cables, or processors with the AOC transceiver:Follow below rules:
Transceivers (AOC ≥ 100 GbE):
  • 100GBase-SR4 QSFP28 Transceiver

  • The ambient temperature must be limited to 30°C or lower and standard fan-packs must be installed.

  • The ambient temperature must be limited to 35°C or lower and high-performance fan-packs must be installed.

Transceivers (AOC ≥ 100 GbE):
  • Mellanox HDR IB Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • Mellanox HDR IB to 2x HDR100 Splitter Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • ThinkSystem NDR OSFP400 IB Multi Mode Solo-Transceiver

  • ThinkSystem NDR/NDR200 QSFP112 IB Multi Mode Solo-Transceiver

  • If TruDDR5 8800MHz 64 GB (2Rx4) MRDIMM or TruDDR5 6400MHz 256 GB (4Rx4) 3DS RDIMM is installed:
    • The ambient temperature must be limited to 25°C or lower and high-performance fan-packs must be installed.

    • The ambient temperature must be limited to 30°C or lower and ultra fan-packs must be installed.

  • If TruDDR5 8800MHz 64 GB (2Rx4) MRDIMM or TruDDR5 6400MHz 256 GB (4Rx4) 3DS RDIMM is not installed:

    • The ambient temperature must be limited to 30°C or lower and high-performance fan-packs must be installed.

Transceivers (AOC ≥ 100 GbE):
  • ThinkSystem NVIDIA ConnectX-8 8240 400GbE / 400Gb/s IB QSFP112 2-port PCIe Gen6 x16 (Generic FW)

  • For 10 x 2.5'' SAS/SATA/NVMe/AnyBay and 6 x 2.5'' SAS/SATA + 4 x 2.5'' AnyBay configuration:
    • The ambient temperature must be limited to 25°C or lower, TDP should be between 300 and 350 Watt, and high-performance fan-packs must be installed.

    • The ambient temperature must be limited to 30°C or lower, TDP should be limited to 300 Watt or lower, and high-performance fan-packs must be installed.

  • For 8 x 2.5'' NVMe/AnyBay/SAS/SATA and 4 x 2.5'' NVMe/SAS/SATA configuration, the ambient temperature must be limited to 30°C or lower, TDP should be limited to 350 Watt or lower, and high-performance fan-packs must be installed.

Processor
  • 6732P

  • The standard heat sinks or high-performance heat sinks cannot be installed.

Note
The following adapters do not support AOC ≥ 100 GbE.
  • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 PCIe Ethernet Adapter

  • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 OCP Ethernet Adapter

Server models with front drive bays only (E3.S configuration)

Configuration
  • 4 x E3.S 1T / 2 x E3.S 2T

  • 8 x E3.S 1T / 4 x E3.S 2T

  • 12 x E3.S 1T / 6 x E3.S 2T

  • 16 x E3.S 1T / 8 x E3.S 2T

Max. Ambient Temp.

(at sea level)

35°C
CPU TDP (watts)TDP ≤ 165165 < TDP ≤ 350
Heat sinkStandardPerformance
Air bafflex
DIMM capacity≤ 256 GB≤ 256 GB
Fan typePerformancePerformance
Max. DIMM Qty.3232
Note
  • For the special notes about adapters, cables, or processors with the AOC transceiver, see Table 1.

  • The following adapters do not support AOC ≥ 100 GbE.
    • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 PCIe Ethernet Adapter

    • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 OCP Ethernet Adapter

Server models with front and rear drive bays

This section provides thermal information for server models with front and rear drive bays.

Configuration

(Front)

  • 10 x 2.5'' NVMe/SAS/SATA/AnyBay/U.3

Configuration

(Rear)

  • 2 x 2.5'' NVMe/U.3

  • 2 x 2.5'' SAS/SATA SSD

  • 2 x 2.5'' SAS/SATA HDD

  • 2 x 2.5'' NVMe/U.3

  • 2 x 2.5'' SAS/SATA SSD

Max. Ambient Temp.

(at sea level)

35°C30°C
CPU TDP (watts)TDP ≤ 210210 ≤ TDP ≤ 225225 < TDP ≤ 250250 < TDP ≤ 300
Heat sinkStandardPerformancePerformancePerformance
Air bafflexxx
Fan typePerformancePerformancePerformancePerformance
DIMM capacity≤ 256 GB≤ 256 GB≤ 256 GB≤ 256 GB
Max. DIMM Qty.32323232

Configuration

(Front)

  • 10 x 2.5'' NVMe/U.3

Configuration

(Rear)

  • 2 x 2.5'' NVMe/U.3

Max. Ambient Temp.

(at sea level)

30°C25°C
CPU TDP (watts)300 < TDP ≤ 350300 < TDP ≤ 350
Heat sinkPerformancePerformance
Air bafflexx
Fan typeUltraPerformance
DIMM capacity≤ 128 GB≤ 128 GB
Max. DIMM Qty.3232
Note
  • For the special notes about adapters, cables, or processors with the AOC transceiver, see Table 1.

  • The following adapters do not support AOC ≥ 100 GbE.
    • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 PCIe Ethernet Adapter

    • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 OCP Ethernet Adapter

Server models with GPUs

This section provides thermal information for server models installed with GPUs.

Configuration
  • 4 x E3.S 1T / 2 x E3.S 2T

  • 8 x E3.S 1T / 4 x E3.S 2T

  • 12 x E3.S 1T / 6 x E3.S 2T

  • 16 x E3.S 1T / 8 x E3.S 2T

  • Backplane-less configuration

  • 4 x 2.5" SAS/SATA/NVMe

  • 8 x 2.5" NVMe/SAS/SATA/AnyBay/U.3

  • 10 x 2.5" NVMe/SAS/SATA/AnyBay/U.3

  • 6 x 2.5" SAS/SATA + 4 x 2.5 AnyBay

  • Backplane-less configuration

  • 4 x 2.5" SAS/SATA/NVMe

  • 8 x 2.5" NVMe/SAS/SATA/AnyBay/U.3

  • 10 x 2.5" NVMe/SAS/SATA/AnyBay/U.3

  • 6 x 2.5" SAS/SATA + 4 x 2.5 AnyBay

Max. Ambient Temp.

(at sea level)

30°C
CPU TDP (watts)TDP ≤ 165165 < TDP ≤ 300300 < TDP ≤ 350165 ≤ TDP ≤ 210
Heat sinkStandardPerformancePerformanceStandard
Air bafflexx
Fan typePerformancePerformancePerformancePerformance
DIMM capacity≤ 256 GB≤ 256 GB≤ 256 GB≤ 256 GB
Max. GPU Qty.3323
Max. DIMM Qty.32323232
Note
  • For the special notes about adapters, cables, or processors with the AOC transceiver, see Table 1.

  • The following adapters do not support AOC ≥ 100 GbE.
    • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 PCIe Ethernet Adapter

    • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 OCP Ethernet Adapter

Server models with NeptAir module

This section provides thermal information for server models installed with the Processor Neptune Air Module (NeptAir).

Configuration

Note1,2

  • Backplane-less configuration

  • 4 x 2.5'' NVMe/SAS/SATA

  • 8 x 2.5'' NVMe/SAS/SATA/AnyBay/U.3

  • 10 x 2.5'' NVMe/SAS/SATA/AnyBay/U.3

  • 6 x 2.5" SAS/SATA + 4 x 2.5 AnyBay

  • 4 x E3.S 1T / 2 x E3.S 2T

  • 8 x E3.S 1T / 4 x E3.S 2T

  • 12 x E3.S 1T / 6 x E3.S 2T

  • 16 x E3.S 1T / 8 x E3.S 2T

Max. Ambient Temp.

(at sea level)

35°C
CPU TDP (watts)TDP ≤ 165165 < TDP ≤ 350300 < TDP ≤ 350
Heat sinkProcessor Neptune Air Module (NeptAir)
Air bafflexxx
Fan typePerformancePerformanceUltra
DIMM capacity≤ 256 GB≤ 128 GB≤ 256 GB
Max. DIMM Qty.323232
Table 2. Special notes
When the server is installed with below adapters, cables, or processors with the AOC transceiver:Follow below rules:
Transceivers (AOC ≥ 100 GbE):
  • 100GBase-SR4 QSFP28 Transceiver

  • The ambient temperature must be limited to 30°C or lower and high-performance fan-packs must be installed.

  • The ambient temperature must be limited to 35°C or lower and ultra fan-packs must be installed.

Transceivers (AOC ≥ 100 GbE):
  • Mellanox HDR IB Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • Mellanox HDR IB to 2x HDR100 Splitter Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • ThinkSystem NDR OSFP400 IB Multi Mode Solo-Transceiver

  • ThinkSystem NDR/NDR200 QSFP112 IB Multi Mode Solo-Transceiver

  • If TruDDR5 8800MHz 64 GB (2Rx4) MRDIMM or TruDDR5 6400MHz 256 GB (4Rx4) 3DS RDIMM is installed:
    • The ambient temperature must be limited to 25°C or lower and high-performance fan-packs must be installed.

    • The ambient temperature must be limited to 30°C or lower and ultra fan-packs must be installed.

  • If TruDDR5 8800MHz 64 GB (2Rx4) MRDIMM or TruDDR5 6400MHz 256 GB (4Rx4) 3DS RDIMM is not installed:

    • The ambient temperature must be limited to 30°C or lower and high-performance fan-packs must be installed.

Transceivers (AOC ≥ 100 GbE):
  • ThinkSystem NVIDIA ConnectX-8 8240 400GbE / 400Gb/s IB QSFP112 2-port PCIe Gen6 x16 (Generic FW)

  • For 10 x 2.5'' SAS/SATA/NVMe/AnyBay, 6 x 2.5'' SAS/SATA + 4 x 2.5'' AnyBay, and 16 x E3.S 1T / 8 x E3.S 2T configuration:
    • The ambient temperature must be limited to 25°C or lower, TDP should be limited to 350 Watt or lower, and high-performance fan-packs must be installed.

    • The ambient temperature must be limited to 30°C or lower, TDP should be limited to 350 Watt or lower, and ultra fan-packs must be installed.

    • The ambient temperature must be limited to 30°C or lower, TDP should be limited to 300 Watt or lower, and high-performance fan-packs must be installed.

  • For 8 x 2.5'' NVMe/AnyBay/SAS/SATA, 4 x 2.5'' NVMe/SAS/SATA, 4 x E3.S 1T / 2 x E3.S 2T, 8 x E3.S 1T / 4 x E3.S 2T, 12 x E3.S 1T / 6 x E3.S 2T, configuration, the ambient temperature must be limited to 30°C or lower, TDP should be limited to 350 Watt or lower, and high-performance fan-packs must be installed.

Processor
  • 6732P

  • The standard heat sinks or high-performance heat sinks cannot be installed.

  • The ambient temperature must be limited to 30°C or lower and high-performance or ultra fan-packs must be installed.

Note
For the special notes about adapters, cables, or processors with the AOC transceiver, see Table 1.

Server models with NeptCore module

This section provides thermal information for server models installed with the Processor Neptune Core Module.

Configuration
  • Backplane-less configuration

  • 4 x 2.5'' NVMe/SAS/SATA

  • 8 x 2.5'' NVMe/SAS/SATA/AnyBay/U.3

  • 10 x 2.5'' NVMe/SAS/SATA/AnyBay/U.3

  • 6 x 2.5" SAS/SATA + 4 x 2.5 AnyBay

  • 4 x E3.S 1T / 2 x E3.S 2T

  • 8 x E3.S 1T / 4 x E3.S 2T

  • 12 x E3.S 1T / 6 x E3.S 2T

  • 16 x E3.S 1T / 8 x E3.S 2T

CPU TDP (watts)TDP ≤ 350

Max. Ambient Temp.

(at sea level)

35°C

Max. Liquid1 inlet Temp.

(at sea level)

45°C
Heat sinkProcessor Neptune Core Module
Air bafflex
Fan typeStandard 2
DIMM capacity≤ 256 GB
Max. DIMM Qty.32
Note
  1. The liquid flow rate for de-ionized water should be no less than 0.5 liters per minute (lpm).

  2. When the server is installed with rear M.2 NVMe/SATA drive or front M.2 NVMe drive assembly, users must install an M.2 drive heat sink.

When the server is installed with below adapters or memory with the AOC transceiver:Follow below rules:
Transceivers (AOC ≥ 100 GbE):
  • 100GBase-SR4 QSFP28 Transceiver

  • The ambient temperature must be limited to 35°C or lower and standard fan-packs must be installed.

Transceivers (AOC ≥ 100 GbE):
  • Mellanox HDR IB Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • Mellanox HDR IB to 2x HDR100 Splitter Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • ThinkSystem NDR OSFP400 IB Multi Mode Solo-Transceiver

  • ThinkSystem NDR/NDR200 QSFP112 IB Multi Mode Solo-Transceiver

  • If TruDDR5 8800MHz 64 GB (2Rx4) MRDIMM or TruDDR5 6400MHz 256 GB (4Rx4) 3DS RDIMM is installed:
    • The ambient temperature must be limited to 30°C or lower and standard fan-packs must be installed.

    • The ambient temperature must be limited to 35°C or lower and high-performance fan-packs must be installed.

  • If TruDDR5 8800MHz 64 GB (2Rx4) MRDIMM or TruDDR5 6400MHz 256 GB (4Rx4) 3DS RDIMM is not installed:

    • The ambient temperature must be limited to 35°C or lower and standard fan-packs must be installed.

Transceivers (AOC ≥ 100 GbE):
  • ThinkSystem NVIDIA ConnectX-8 8240 400GbE / 400Gb/s IB QSFP112 2-port PCIe Gen6 x16 (Generic FW)

  • The ambient temperature must be limited to 35°C or lower and standard fan-packs must be installed.

Note
The following adapters do not support AOC ≥ 100 GbE.
  • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 PCIe Ethernet Adapter

  • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 OCP Ethernet Adapter

Server models with Compute Complex Neptune Core Module

This section provides thermal information for server models installed with the Compute Complex Neptune Core Module.

Configuration
  • Backplane-less configuration

  • 4 x 2.5'' NVMe/SAS/SATA

  • 8 x 2.5'' NVMe/SAS/SATA/U.3

  • 10 x 2.5'' NVMe/SAS/SATA/U.3

  • 4 x E3.S 1T

  • 8 x E3.S 1T

  • 12 x E3.S 1T

CPU TDP (watts)TDP ≤ 350

Max. Ambient Temp.

(at sea level)

35°C

Max. Liquid1 inlet Temp.

(at sea level)

45°C
Heat sinkCompute Complex Neptune Core Module
Air bafflex
Fan typeStandard 2
DIMM capacity≤ 256 GB
Max. DIMM Qty.16
Note
  1. The liquid flow rate for de-ionized water should be no less than 0.5 liters per minute (lpm).

  2. When the server is installed with rear M.2 NVMe/SATA drive or front M.2 NVMe drive assembly, users must install an M.2 drive heat sink.

When the server is installed with below adapters with the AOC transceiver:Follow below rules:
Transceivers (AOC ≥ 100 GbE):
  • 100GBase-SR4 QSFP28 Transceiver

  • The ambient temperature must be limited to 35°C or lower and standard fan-packs must be installed.

Transceivers (AOC ≥ 100 GbE):
  • Mellanox HDR IB Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • Mellanox HDR IB to 2x HDR100 Splitter Optical QSFP56 Cable (3m/5m/10m/15m/20m)

  • ThinkSystem NDR OSFP400 IB Multi Mode Solo-Transceiver

  • ThinkSystem NDR/NDR200 QSFP112 IB Multi Mode Solo-Transceiver

  • The ambient temperature must be limited to 30°C or lower.

Transceivers (AOC ≥ 100 GbE):
  • ThinkSystem NVIDIA ConnectX-8 8240 400GbE / 400Gb/s IB QSFP112 2-port PCIe Gen6 x16 (Generic FW)

  • The ambient temperature must be limited to 35°C or lower and standard fan-packs must be installed.

Note
The following adapters do not support AOC ≥ 100 GbE.
  • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 PCIe Ethernet Adapter

  • ThinkSystem Broadcom 57608 2x200/1x400GbE QSFP112 OCP Ethernet Adapter