Thermal rules for server without DWCM
This topic provides thermal rules for the server with 9004 series processors and without a Direct Water Cooling Module (DWCM).
Max.Temp.: Maximum ambient temperature at sea level
FIO = riser 5 + front OCP
S/S: SAS/SATA
Any: AnyBay
S: standard
P: performance
A: advanced
NA: not applicable
Y: yes
Y* in the Support middle bays or Support rear bays column: yes (when no Gen5 7.68 TB or larger capacity NVMe drive or no Gen4 P5336 15.36 TB/30.72 TB/61.44 TB NVMe drive is installed)
Y1 in the Support DIMMs >= 96 GB column: yes (except ThinkSystem 128GB TruDDR5 4800MHz (4Rx4) 3DS RDIMM-A v1)
N: no
Group B: 200 W ≤ cTDP ≤ 240 W
Group A: 240 W < cTDP ≤ 300 W
Group E: 320 W ≤ cTDP ≤ 400 W
Group E1: 9654(P), 9554(P), 9174F, 9754, 9734, and 9684X.
Group E2: 9654(P), 9554(P), 9174F, 9754, and 9734.
Group E3: 9184X and 9384X
For 9184X or 9384X in UEFI Maximum Performance Mode, the processor temperature may reach 95°C in all configurations, and the processor frequency will be impacted but still meets AMD specifications.
- ThinkSystem NVIDIA BlueField-3 VPI QSFP112 2P 200G PCIe Gen5 x16 is supported under the following conditions:
The ambient temperature is 25°C or lower.
The processor TDP is less than or equal to 300 W.
The GPU air baffle and performance fans are used.
The server is not equipped with 24 x 2.5", 16 x 2.5" + FIO, or 12 x 3.5" front drive bays.
Performance fans are needed for all GPU configurations.
The GPU air baffle is needed in configurations that include adapters with power greater than 75 W. No air baffle is needed in configurations with middle drive bays.
Standard configurations
When a part with active optical cable (AOC) is installed and the rate of the part is greater than 25 GB, the ambient temperature must be limited to 30°C or lower.
When the following parts are installed, the ambient temperature must be limited to 35°C or lower.
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP
Network interface cards (NICs) at a rate greater than or equal to 100 GB
Parts with AOC and at the rate of 25 GB
In standard configurations, ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1 is supported only on servers with standard heat sinks at a maximum temperature of 25°C.
Front bays | Max. Temp. | Processor | Heat sink | Fan type | Support DIMMs >= 96 GB |
---|---|---|---|---|---|
| 45°C | Group B | 2U P | P | N |
35°C | Group B | 2U S | S | N | |
Group B, A | 2U S | P | Y | ||
Group E1, E3 | 2U A | P | Y1 | ||
30°C | Group B, A | 2U S | P | Y | |
Group E1 | 2U P | P | Y1 | ||
Group E | 2U A | P | Y1 | ||
25°C | Group B, A | 2U S | P | Y | |
Group E | 2U P | P | Y |
Storage configurations
- A part with AOC and at a rate greater than 25 GB is supported under the following conditions:
Performance fans are used.
The part is not installed on slot 3.
The following parts are not supported in storage configurations:
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP
Storage configurations do not support ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1.
Front bays | Support middle bays | Support rear bays | Max. Temp. | Processor | Heat sink | Fan type | Support DIMMs >= 96 GB |
---|---|---|---|---|---|---|---|
24 x 2.5" 16 x 2.5" + FIO | N | N | 30°C | Group B | 2U S | S | N |
N | N | 30°C | Group B | 2U S | P | Y | |
N | N | 30°C | Group A | 2U P | P | Y1 | |
N | N | 30°C | Group E | 2U A | P | Y1 | |
N | N | 25°C | Group B | 2U S | P | Y | |
N | N | 25°C | Group A, E2 | 2U P | P | Y1 | |
N | N | 25°C | Group E3, 9684X | 2U A | P | Y1 | |
N | Y* | 30°C | Group B | 2U P | P | Y1 | |
Y* | N | 30°C | Group B | 2U P | P | Y1 | |
Y* | Y* | 30°C | Group B | 2U P | P | Y1 | |
N | Y | 25°C | Group B, A | 2U P | P | Y | |
Y | N | 25°C | Group B, A | 2U P | P | Y | |
Y | Y | 25°C | Group B, A | 2U P | P | Y | |
12 x 3.5" | N | N | 30°C | Group B | 2U S | P | Y |
N | N | 30°C | Group A | 2U P | P | Y1 | |
N | N | 30°C | Group E | 2U A | P | Y1 | |
N | Y* | 30°C | Group B | 2U P | P | Y1 | |
Y* | N | 30°C | Group B | 2U P | P | Y1 | |
Y* | Y* | 30°C | Group B | 2U P | P | Y1 | |
N | Y | 25°C | Group B, A | 2U P | P | Y | |
Y | N | 25°C | Group B, A | 2U P | P | Y | |
Y | Y | 25°C | Group B, A | 2U P | P | Y |
GPU configurations without FIO
This section provides thermal information for the GPU configurations without FIO.
Half-height half-length (HHHL) single-wide (SW) GPU: A2, L4
HHHL double-wide (DW) GPU: A2000
Full-height full-length (FHFL) DW GPU: A30, A4500, A16, A40, A100, A6000, L40, L40S, H100, RTX 6000 Ada, RTX 4500 Ada, H100 NVL, AMD MI210
- For GPU configurations, the Max. Temp. of 25°C is supported under the following conditions:
A part with AOC and at a rate greater than 25 GB is not installed in slot 3.
The following parts are not installed:
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP
In GPU configurations without FIO, ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1 is supported only on servers with 8 x 2.5"/16 x 2.5"/8 x 3.5" front bays and Group B processors at a maximum temperature of 25°C.
- The H100 NVL GPU adapter is supported in a non-24x2.5" GPU configuration under the following conditions:
The processor TDP is less than or equal to 300 W.
The ambient temperature is 25°C or lower.
Front bays | Max. Temp. | Processor | Heat sink | Air baffle | Max. GPU Qty. | Support DIMMs >= 96 GB | ||||
---|---|---|---|---|---|---|---|---|---|---|
A2/L4 | A2000 | A40/L40 | 350W DW | Other DW | ||||||
8 x 2.5" | 30°C | Group B | 2U S | S | 10 | 3 | NA | NA | NA | Y |
Group A | 2U P | S | 10 | 3 | NA | NA | NA | Y1 | ||
Group B, A | 2U P | GPU | NA | NA | 3 | 3 | 3 | Y | ||
25°C | Group E1, E3 | 2U P | S | 6 | 3 | NA | NA | NA | Y | |
Group E1, E3 | 2U P | GPU | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 2 (slot 2/5) | Y | ||
16 x 2.5" | 30°C | Group B | 2U S | S | 10 | 3 | NA | NA | NA | Y |
Group A | 2U P | S | 10 | 3 | NA | NA | NA | Y1 | ||
Group B, A | 2U P | GPU | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 3 | Y | ||
25°C | Group E1, E3 | 2U P | S | 6 | 3 | NA | NA | NA | Y | |
Group E1, E3 | 2U P | GPU | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 2 (slot 2/5) | Y | ||
8 x 3.5" | 30°C | Group B | 2U S | S | 10 | 3 | NA | NA | NA | Y |
Group A | 2U P | S | 10 | 3 | NA | NA | NA | Y1 | ||
Group B, A | 2U P | GPU | NA | NA | 3 | 3 | 3 | Y | ||
25°C | Group E1, E3 | 2U P | S | 6 | 3 | NA | NA | NA | Y | |
Group E1, E3 | 2U P | GPU | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 2 (slot 2/5) | Y | ||
24 x 2.5" | 25°C | Group B | 2U S | S | 6 | 3 | NA | NA | NA | Y |
Group A | 2U P | S | 6 | 3 | NA | NA | NA | Y1 | ||
Group B, A | 2U P | GPU | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | 2 (slot 2/5) | Y |
GPU configurations with FIO
This section provides thermal information for the GPU configurations with FIO.
Half-height half-length (HHHL) single-wide (SW) GPU: A2, L4
HHHL double-wide (DW) GPU: A2000
Full-height full-length (FHFL) DW GPU: A30, A4500, A16, A40, A100, A6000, L40, L40S, H100, RTX 6000 Ada, RTX 4500 Ada, H100 NVL, AMD MI210
- For GPU configurations, the Max. Temp. of 25°C is supported under the following conditions:
A part with AOC and at a rate greater than 25 GB is not installed in slot 3.
The following parts are not installed:
Broadcom 57416 10GBASE-T 2-port OCP
Broadcom 57454 10GBASE-T 4-port OCP
In GPU configurations with FIO, ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1 is supported only on servers with FIO or FIO + 8 x 2.5" front bays and Group B processors at a maximum temperature of 25°C.
- The H100 NVL GPU adapter is supported only in GPU configurations with FIO only or FIO + 8 x 2.5" front bays under the following conditions:
The processor TDP is less than or equal to 300 W.
The ambient temperature is 25°C or lower.
Front bays | Max. Temp. | Processor | Heat sink | Air baffle | Max. GPU Qty. | Support DIMMs >= 96 GB | ||||
---|---|---|---|---|---|---|---|---|---|---|
A2/L4 | A2000 | A40/L40 | 350W DW | Other DW | ||||||
FIO only FIO + 8 x 2.5" | 30°C | Group B | 2U S | S | 10 | 3 | NA | NA | NA | Y |
Group A | 2U P | S | 10 | 3 | NA | NA | NA | Y1 | ||
Group B, A | 2U P | GPU | NA | NA | 2 (slot 2/5) | 3 | 3 | Y | ||
25°C | Group B | 2U S | S | 6 | 3 | NA | NA | NA | Y | |
Group E1 | 2U P | S | 6 | 3 | NA | NA | NA | Y | ||
Group E1 | 2U P | GPU | NA | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | Y | ||
FIO + 16 x 2.5" | 25°C | Group B | 2U S | S | 6 | 3 | NA | NA | NA | Y |
Group A | 2U P | S | 6 | 3 | NA | NA | NA | Y1 | ||
Group B, A | 2U P | GPU | NA | NA | NA | 2 (slot 2/5) | 2 (slot 2/5) | Y |