Skip to main content

0821C003 : Power supply [arg1] has exceeded the warning temperature.

Power supply [arg1] has exceeded the warning temperature.

The temperature of the specified power supply has exceeded the warning threshold. The system is currently operating within the allowed temperature range. However, an additional rise in temperature might result in the shutdown of devices in the chassis.

Severity

Warning

Alert Category

Power Modules (Warning)

Log Source

Power_03

Serviceable

Yes

Recoverable

Yes

Chassis LED that is Lit

None

CIM Information

Prefix:CMM

and ID:0024

SNMP Trap ID

mmTrapPowerN

Automatically Notify Support

No

User Response

Complete the following steps until the problem is solved:

  1. Check the Chassis Management Module event log for any events related to the fan modules, and solve those events.
  2. Check the ambient room temperature to ensure that the room is not too hot.
  3. Check for any blockage on or near the ventilation holes on the chassis. Remove any blockages that you find.
  4. Make sure that a device or filler is installed in each bay in the front and rear of the chassis, and make sure that nothing is covering the bays. Empty bays can cause a reduction in airflow to the devices in the chassis.
  5. Check the ambient chassis temperature. Make sure that enough fan modules are installed to sufficiently cool the devices in the chassis. See the chassis documentation to determine how many fan modules should be installed.
  6. Check the status of the specified power supply. If the internal fan has failed, replace the power supply.