4062500B : Node [arg1] system-management processor failed initialization to allow monitoring.
Node [arg1] system-management processor failed initialization to allow monitoring.
The system-management processor of the specified node did not provide adequate information during the initialization sequence. The node will not be monitored.
Severity
Error
Alert Category
Nodes (Critical)
Log Source
Node_11
Serviceable
Yes
Recoverable
Yes
Chassis LED that is Lit
None
SNMP Trap ID
mmTrapBladeC
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- If more than one node is having this problem, reset the CMM, or fail over the CMM to the standby CMM if two CMMs are installed.
- Check the event logs and any status indicators for the node for possible additional information about the problem. Follow the troubleshooting instructions in the information center or Installation and Service Guide for the node that is reporting the event. Check the documentation for any applications that are running for application-specific troubleshooting instructions.
- Perform a hard restart of the node system-management processor.
- Perform a virtual reseat of the node. Attention: A virtual reseat shuts down power to the node. Check the interfaces of applications that are running to make sure that the node can be shut down safely.
Give documentation feedback