0EA1C404 : I/O module [arg1] temperature fault.
I/O module [arg1] temperature fault.
The temperature of the specified I/O module has exceeded the fault threshold, and the I/O module will shut down. The fan modules in the affected cooling zone will run at full speed.
Severity
Error
Alert Category
I/O Modules (Critical)
Log Source
IOMod_04
Serviceable
Yes
Recoverable
Yes
Chassis LED that is Lit
Chassis Fault
SNMP Trap ID
mmTrapIOC
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- Check the Chassis Management Module event log for any events related to the fan modules, and solve those events.
- Check the ambient room temperature to ensure that the room is not too hot.
- Check for any blockage on or near the ventilation holes on the chassis. Remove any blockages that you find.
- Make sure that a device or filler is installed in each bay in the front and rear of the chassis, and make sure that nothing is covering the bays. Empty bays can cause a reduction in airflow to the devices in the chassis.
- Check the ambient chassis temperature. Make sure that enough fan modules are installed to sufficiently cool the devices in the chassis. See the chassis documentation to determine how many fan modules should be installed.